In:
Advanced Materials Research, Trans Tech Publications, Ltd., Vol. 446-449 ( 2012-1), p. 621-625
Abstract:
In order to analyze aseismic behavior of the high reinforced concrete (R.C.) shear wall with frame column in the large thermal power plant, the model structure has been taken test with method of low frequency cyclic repeated load that has 1/15 scaling factor to practical structure. At same time the model has been analyzed by the finite element method which takes the Hognestad concrete constitutive model and ideal elastic-plasticity steel reinforcement constitutive equation. It has been found that the hysteretic curve is relatively full and energy dissipation capacity is better through the experiment. The bearing capacity, deformation and fracture results to the Shear wall of finite element analysis are closely with the test results. In general, the R.C. shear wall with frame column in the large thermal power plant has good aseismic performance. The finite element method can be taken to analyzed the similarity structure.
Type of Medium:
Online Resource
ISSN:
1662-8985
DOI:
10.4028/www.scientific.net/AMR.446-449
DOI:
10.4028/www.scientific.net/AMR.446-449.621
Language:
Unknown
Publisher:
Trans Tech Publications, Ltd.
Publication Date:
2012
detail.hit.zdb_id:
2265002-7